Voltage Drop Calculator

Size a run against the NEC's 3% recommendation. Updates as you type.

Voltage drop
-
% drop
-
Volts at load
-

How it's figured

Single-phase: VD = (2 × K × I × L) ÷ circular mils. Three-phase uses √3 instead of 2. K ≈ 12.9 (copper) / 21.2 (aluminum) ohms·cmil/ft. The NEC recommends ≤3% on a branch circuit (≤5% total feeder + branch) in informational notes. It's guidance, not a hard rule.

Informational only. This is not legal advice, and not an official government resource. Licensing rules change; always confirm against the official board source linked on this page before you renew, apply, or make a business decision. Trade Cert Hub is independent and not affiliated with any state licensing board. Some links are affiliate links, and we may earn a commission at no extra cost to you (full disclosure).